| Power rating |
300 W |
| Output voltage |
24 VDC |
| Efficiency |
82 % typ. (at 100 VAC input) 87 % typ. (at 200 VAC input) 87 % typ. (at 230 VAC input) |
| Input |
Rated input voltage |
100 to 240 VAC |
| Allowable input voltage variable range |
85 to 264 VAC (Single-phase) 120 to 370 VDC |
| Frequency |
50/60Hz (47 to 63 Hz) |
| Rated input current |
4.2 A typ. (at 100 VAC input) 2.1 A typ. (at 200 VAC input) |
| Power factor |
0.9 min. |
| Leakage current |
0.5 mA max. (at 100 VAC input) 1 mA max. (at 200 VAC input) |
| Inrush current (cold start at 25 ℃) |
14 A typ. (at 100 VAC input) 28 A typ. (at 200 VAC input) |
| Output |
Rated output current |
14 A |
| Output voltage variable range |
-10 to +15 % (With V.ADJ) |
| Ripple |
150 mV(p-p) max. |
| Static input variation influence |
0.5 % max. |
| Static load variation influence |
1.0 % max. |
| Ambient temperature variation influence |
0.05 %/℃ max. |
| Start up time |
1000 ms max. (at 100 VAC input) 1000 ms max. (at 200 VAC input) |
| Hold time |
40 ms typ. (at 100 VAC input) 40 ms typ. (at 200 VAC input) |
| Additional functions |
Overload protection |
Yes, automatic reset |
| Overvoltage protection |
Yes, Shut off the input voltage and turn on the input again |
| Overheat protection |
Yes, Shut off the input voltage and turn on the input again |
| Series operation |
Yes (Up to 2 Power Supplies with external diode) |
| Parallel operation |
No (However, backup operation is possible, external diodes required.) |
| Output indicator |
Yes (color: green) |
| Insulation |
Dielectric strength |
Between all input terminals and all output terminals: 3 kVAC for 1 min, Cut-off current: 20 mA Between all input terminals and PE terminals: 2 kVAC for 1 min, Cut-off current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Cut-off current: 20 mA |
| Insulation resistance |
Between all output terminals and all input terminals/PE terminals: 100 MΩ min., at 500 VDC |
| Environment |
Vibration resistance |
10 to 55 Hz, 4.5 G max., 0.375 mm single amplitude in each 3 directions for 2 hours |
| Shock resistance |
150 m/s2, in each 6 directions 3 times |
| Altitude |
3000 m max. |
| Ambient temperature (Operating) |
-20 to 70 ℃ (with no freezing or condensation) |
| Ambient temperature (Storage) |
-25 to 75 ℃ (with no freezing or condensation) |
| Ambient humidity (Operating) |
90 %RH max. |
| Ambient humidity (Storage) |
90 %RH max. |
| Reliability |
Life expectancy |
10 years min. (at rated input, a load rate of 50% load, under the temperature of 40 ℃ max., standard mounting) |
| Construction |
Construction |
Covered type |
| Connection |
Terminal blocks |
| Terminal type |
Screw terminal |
| Mounting |
DIN track mounting |
| Cooling fan |
Cooling fan Yes |
| Weight (Main) |
700 g max. |