Contact resistance |
100 mΩ max. (Voltage drop method with 5 VDC 1 A) |
Operating time |
20 ms max. (With rated operating power applied, 23 ℃, not including contact bounce) |
Reset time |
20 ms max. (With rated operating power applied, 23 ℃, not including contact bounce) |
Maximum operating frequency |
Mechanical: 36000 time/hour Rated load: 1800 time/hour |
Insulation resistance |
Between coil and contacts: 1000 MΩ min. (at 500 VDC) Between contacts of different polarity: 1000 MΩ min. (at 500 VDC) Between contacts of same polarity: 1000 MΩ min. (at 500 VDC) |
Dielectric strength |
Between coil and contacts: 4000 VAC 50/60 Hz 1 min Between contacts of different polarity (Between pole 3 and pole 5_pole 4 and pole 6_pole 5 and pole 6): 2500 VAC 50/60 Hz 1 min Between contacts of different polarity (Except for between pole 3 and pole 5_pole 4 and pole 6_pole 5 and pole 6): 4000 VAC 50/60 Hz 1 min Between contacts of same polarity: 1500 VAC 50/60 Hz 1 min |
Vibration resistance (destruction) |
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
Vibration resistance (Malfunction) |
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
Shock resistance (destruction) |
1000 m/s2
|
Shock resistance (Malfunction) |
100 m/s2
|
Endurance (Mechanical) |
10,000,000 operations min. (switching frequency 36,000 operations/h) |
Endurance (Electrical) |
100,000 operations min. (rated load) |
Failure rate |
5 VDC 1 mA (failure level: Preference value, Switching frequency: 300 operations per minute) |
Ambient temperature (Operating) |
-40 to 85 ℃ (with no freezing or condensation) |
Ambient humidity (Operating) |
5 to 85 % |
Weight |
Approx. 25 g |
Mounting method |
Socket, Soldering |
Applicable socket |
P7SA-14F/ P7SA-14F-ND/ P7SA-14P/ P7SA-14F-ND-PU |