| Height |
42 mm |
| Width |
30 mm |
| Depth |
52 mm |
| Terminals description ISO n°1 |
(13-14)NO |
| Net weight |
0.037 kg |
| Device mounting |
Fixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to IEC 60957-5-1 |
| Fixing mode |
Fixing nut recommended torque: 2.2 N.m (+/- 0.2 N.m) |
| Contacts usage |
Standard contacts |
| Positive opening |
Without |
| Operating travel |
1.5 mm (NC changing electrical state) 2.6 mm (NO changing electrical state) 4.3 mm (total travel) |
| Operating force |
3.5 N NC changing electrical state 3.8 N NO changing electrical state |
| Mechanical durability |
5000000 cycles |
| Tightening torque |
0.8…1.2 N.m conforming to IEC 60947-1 |
| Shape of screw head |
Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
| Contacts material |
Silver alloy (Ag/Ni) |
| Short-circuit protection |
10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
| [Ith] conventional free air thermal current |
10 A conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-1 |
| [Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 |
| Electrical durability |
1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles AC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C |
| Electrical reliability |
Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4 Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4 |
| Device presentation |
Complete product |
| Customizable |
No |
| Customizable |
0 |
| Compatibility code |
XB5 |