DELIVERY PERIOD : 1-2 WEEKS
• Models of width 17.5 mm available with 2 or 3 poles. Models of width 22.5 mm with 3 poles also available.
• Conforms to EN standards. (TÜV approval)
• DIN track mounting possible.
Power Input
Model |
G9SB-200[]-[] |
G9SB-3010 |
G9SB-301[]-[] |
Power supply voltage |
24 VAC/24 VDC |
24 VDC |
24 VAC/24 VDC |
Operating voltage range |
85% to 110% of rated power supply voltage |
Power consumption |
2.9 VA/1.4 W max. |
1.7 W max. |
3.6 VA/1.7 W max. |
Inputs
Model |
G9SB-200[]-[] |
G9SB-3010 |
G9SB-301[]-[] |
Input current |
25 mA max. |
60 mA max. * |
30 mA max. |
* Indicates the current between terminals A1 and A2.
Contacts
Model Load |
G9SB-200[]-[] |
G9SB-3010 |
G9SB-301[]-[] |
Resistive load |
Rated load |
250 VAC, 5 A 30 VDC, 5 A |
Rated carry current |
5 A |
Characteristics
Model |
G9SB-200[]-[] |
G9SB-3010 |
G9SB-301[]-[] |
Contact resistance *1 |
100 mΩ |
Operating time *2 |
30 ms max. |
Response time *3 |
10 ms max. |
Isolation voltage (Ui) |
250 V/AC |
Impulse withstand voltage (Uimp) |
4 kV |
Insulation resistance *4 |
Between inputs and outputs |
100 MΩ min. (at 500 VDC) |
Between different poles of output |
Dielectric strength |
Between inputs and outputs |
2,500 VAC 1 min. |
Between different poles of output |
Vibration resistance |
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) |
Shock resistance |
Destruction |
300 m/s2
|
Malfunction |
100 m/s2
|
Durability *5 |
Mechanical |
5,000,000 operations min. (at approx. 7,200 operations/hr) |
Electrical |
100,000 operations min. (at approx. 1,800 operations/hr) |
Failure rate (P level) (reference value) |
5 VDC, 1 mA |
Ambient operating temperature |
-25 to 55°C (with no icing or condensation) |
Ambient operating humidity |
35% to 85% |
Pollution degree |
2 |
Protection class |
IP20 |
Terminal tightening torque |
0.5 N·m |
Weight |
Approx. 115 g |
Approx. 135 g |
Approx. 120 g |
*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
*2. Not including bounce time.
*3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.
*4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
*5. The durability is for an ambient temperature of 15 to 35°C and an ambient humidity of 25% to 75%.